In a small restaurant, shop or office the biggest savings are operational: stop conditioning the space when it is closed, keep the rooftop unit's filters, coils and outside-air damper working, and stop paying to heat or cool air that the kitchen hood or the front door immediately throws away.

How much is there to save

The EPA's Energy Star program has long estimated that the average commercial building wastes about 30% of the energy it uses. Small spaces are rarely average in a good way. They seldom have anyone whose job is the equipment, the thermostat is set by whoever felt cold last, and the rooftop unit is out of sight. That is good news in one sense: most of the waste can be cut without buying anything large.

Fix the schedule first

  • Use a programmable thermostat with separate occupied and unoccupied settings, and set it to your real hours, including the days you are closed.
  • Set the fan to "auto" outside business hours. A fan left on runs the blower and, on many units, pulls in outside air all night.
  • Start conditioning shortly before opening, not hours before. Let the space drift for the last half hour before closing.
  • Lock the thermostat or use a guard with a limited adjustment range. One or two degrees of override is enough for staff.
  • Keep heating and cooling setpoints a few degrees apart so the unit does not flip between the two on a mild day.

What is inside a rooftop unit

1 2 3 4 5 6

A packaged rooftop unit, cut open

  1. Outside-air hood and damper. Brings in ventilation air, and free cooling when it has an economizer.
  2. Filters. The cheapest part and the most neglected.
  3. Cooling coil. Dirt here cuts capacity and airflow.
  4. Supply fan, often belt driven.
  5. Compressor, condenser coil and fan, where the building's heat is thrown out.
  6. Supply and return ducts through the roof curb.

Rooftop unit care that pays for itself

  • Change filters on a fixed schedule, monthly in a kitchen or on a dusty street, at least quarterly elsewhere.
  • Clean the condenser coil every spring. City soot, cottonwood fluff and kitchen grease coat it, and a dirty coil makes the compressor run hotter and longer for the same cooling.
  • Clean the indoor coil and the drain pan, and clear the condensate trap.
  • Check the fan belt for wear and tension, or ask whether a direct-drive or notched-belt upgrade is available.
  • Make sure every access panel is back on with all its screws. A missing panel leaks conditioned air straight to the sky.
  • Have refrigerant charge, electrical connections and gas heat checked by a technician twice a year, before summer and before winter.

Make sure the economizer works

An economizer opens the outside-air damper wide when the air outdoors is cool and dry enough to cool the space on its own, so the compressor can stay off. New York has many such hours in spring, fall and on summer nights, and a kitchen or a crowded shop wants cooling even in cool weather. Economizers fail quietly. A damper stuck shut wastes the free cooling; a damper stuck open drags in July air or January air all day. Ask the technician to make the damper move through its full range and to check its sensor at every visit.

Kitchen exhaust and makeup air

A restaurant hood removes a large volume of air every minute it runs, and all of it has to be replaced. If the replacement comes from the dining room, you are paying to heat or cool that air once and then sending it up the stack.

  • Run hoods only when cooking equipment is on. Variable-speed hood controls that respond to heat and smoke cut fan energy and the amount of conditioned air removed.
  • Keep the makeup-air unit working and its filters clean. When it fails, the kitchen pulls air through the front door and every gap, and the dining room becomes drafty and hard to control.
  • A door that is hard to open, or that whistles, means the space is under negative pressure. Have the air balance checked.
  • Keep grease filters clean so the hood captures at its design airflow.

The front door

An open door on a hot or cold day is the largest leak a shop can have. Keep it closed with a working closer. If the entrance is busy, a vestibule or an air curtain over the door reduces the exchange each time it opens. Weatherstrip the door and the sidewalk cellar hatch, and seal any wall sleeve or old louver that is no longer in use.

Cut the heat you make indoors

Every watt used inside becomes heat the air conditioner must remove. LED lighting, display cases with doors, and switching off cooking equipment between rushes all lower the cooling load. Self-contained coolers and ice machines release their heat into the room; clean condensers help them and the air conditioner at the same time. See the refrigeration guide for the routine.

Know what you are billed for

Many commercial electric rates include a demand charge based on your highest short burst of use in the month, as well as a charge for total energy. Starting the rooftop unit, the ovens and the dish machine in the same fifteen minutes can set a peak you pay for all month. Stagger morning start-up where you can. Ask the utility for your interval data if your meter records it, and compare each bill with the same month a year earlier.

When the unit is due for replacement

A rooftop unit near the end of its life is a chance to fix more than the unit. Have the load recalculated; many are oversized for the space as it is used today. Compare part-load efficiency ratings, since a unit spends most of its hours well below full output, and look at variable-speed fans and compressors. A heat pump rooftop unit can take over heating as well. Confirm roof structure, curb size, crane access and the landlord's requirements early, because in this city getting the unit onto the roof can cost as much thought as choosing it.

Check the lease as well. It normally says who maintains and who replaces the unit, and that decides who should be paying for the service contract.

For the home side of the same subject, see the home cost-saving ideas.