How a mini split works
The outdoor unit holds the compressor and a coil. The indoor unit, usually called a head, holds a second coil and a fan. Refrigerant circulates between them through two insulated copper tubes. In summer the indoor coil absorbs heat from the room and the outdoor coil gets rid of it. In winter a valve reverses the flow, and the system pulls heat out of the outdoor air and releases it indoors.
Nearly all current models are inverter driven. The compressor speeds up and slows down to match the load instead of switching fully on and off, which is why a mini split holds a steadier temperature and makes less noise than a window unit. Efficiency is rated in SEER2 for cooling and HSPF2 for heating; a higher number means less electricity for the same output.
One hole carries everything
- Indoor unit, mounted high on an outside wall where it can blow across the room.
- Core-drilled hole with a sleeve, pitched slightly down toward the outside so water cannot run back in.
- Line set: two insulated copper refrigerant tubes plus a control cable, usually under a cover.
- Condensate drain. It needs a continuous downhill path to a place the building allows water to go.
- Outdoor unit, here on a wall bracket with vibration pads. It needs clear air on the coil side.
Window unit, wall sleeve or mini split
Most New York apartments are cooled by one of three things. Each has a place. The comparison below is about how they behave in the building, not about any one model.
| Window unit | Through-wall sleeve unit or PTAC | Ductless mini split | |
|---|---|---|---|
| What the building has to allow | Usually only a secure installation; many buildings require a support bracket | Nothing new if the sleeve exists; the unit must match the sleeve | An outdoor unit location, a wall penetration and often electrical work |
| Heating | Rare, and weak where offered | PTACs often heat with electric resistance, a heat pump, or the building's steam or hot water | Yes, as a heat pump, including in cold weather on cold-climate models |
| Noise indoors | Loudest: the compressor is in the window | Loud to moderate: compressor is in the wall | Quietest: the compressor is outdoors |
| Efficiency | Lowest to middling (rated in CEER) | Middling (rated in EER) | Highest (rated in SEER2 and HSPF2) |
| What you give up | The window, daylight, and a tight seal in winter | Little, but the sleeve leaks air if it is not sealed | Time and money up front, plus approvals |
| Who installs it | The resident or a handyman | The resident or building staff for a like-for-like swap | A contractor in most buildings |
If the building already has wall sleeves, check the sleeve before shopping. Most PTAC sleeves are a standard 42 by 16 inches, while the smaller through-wall sleeves found under apartment windows come in several sizes, and a unit that does not fit and vent correctly will overheat or leak into the wall.
Getting the lines through masonry
The hole is the part people worry about, and it is the simplest part to do well. A brick or brownstone wall is core drilled, not hammered, so the hole comes out round and clean. Good practice looks like this:
- Locate the hole away from flues, steam risers, gas piping and wiring inside the wall. In old buildings that means checking, not assuming.
- Stay clear of window lintels and other structure. Solid field brick is the place to drill.
- Pitch the hole down toward the outside, line it with a sleeve, and seal around the lines with a material rated for the job so rain, air and pests stay out.
- Keep the line set within the manufacturer's maximum length and maximum height difference, and above its minimum length. Both ends of that range matter.
- Run exposed lines under a UV-resistant cover, fixed to the wall, in the least visible route the building will accept.
Condensate causes more callbacks than refrigerant. In cooling mode the indoor unit can drain a surprising amount of water on a humid day. It should run downhill all the way to an approved discharge point. It should not drip onto a neighbor's window, a sidewalk or a fire escape. Where gravity cannot do it, a small condensate pump can, but a pump is one more part that can fail and it makes a little noise.
Refrigerant, and who can do the work
New mini splits use R-32 or R-454B. Both are classed A2L, meaning mildly flammable, and they replaced R-410A in newly manufactured equipment. That changes little for the resident, but the installer has to follow the manual's limits on charge, room size and line length. Anyone who opens the refrigerant circuit, adds refrigerant or recovers it must hold EPA Section 608 certification.
Some systems are sold for owner installation with factory-charged lines and sealed quick-connect fittings, so the refrigerant circuit is never opened on site. Zone Air, for one, supplies pre-charged quick-connect line sets cut to the length each room needs, from 5 to 75 ft, which matters on a narrow roof or bracket where there is nowhere to coil spare tubing. A do-it-yourself system does not change what the building requires. The outdoor location, the wall penetration and the new electrical circuit still need the same consent, and the wiring is still an electrician's job.
Heating with a mini split
A mini split is a heater as much as an air conditioner. Models built for cold climates keep most of their capacity when it is well below freezing, and the city's winter design temperature sits in the teens Fahrenheit, which is within their range. Check the capacity the manufacturer lists at 17°F and at 5°F, not just the headline number.
In heating mode the outdoor unit collects frost and periodically melts it off. That meltwater needs somewhere to go that will not turn into a sheet of ice on a roof walkway or a neighbor's yard. Keep the unit raised above expected snow.
In a steam building a mini split usually works alongside the radiators: it carries fall and spring on its own and takes the edge off rooms the steam misses. The steam and boiler guide covers how the two fit together.
Upkeep
- Wash the indoor filters every few weeks in heavy use. A clogged filter is the usual cause of weak airflow and ice on the coil.
- Keep the outdoor coil clear of leaves, plastic bags and anything stored against it.
- Watch the drain. Water marks under the indoor unit mean the drain is blocked or has lost its pitch.
- Have the coils and drain pan cleaned professionally every year or two; city air is dirty.
Next: where the outdoor unit can go, who approves it, and how to size each room. If you want cooling through ceiling grilles with no unit on the wall, see central air in New York housing.