Teletemp

Commercial refrigeration basics for restaurants and delis

Most refrigeration failures in a restaurant or deli start as an airflow or heat problem that anyone can spot: a condenser coil matted with grease and dust, a door that no longer seals, or an evaporator buried in ice. Cleaning coils and checking gaskets on a schedule prevents the majority of emergency calls.

How a cooler makes cold

A refrigeration system does not create cold. It moves heat from inside the box to somewhere else. The evaporator coil inside the box absorbs heat from the air and the food. The compressor pumps that heat, carried by the refrigerant, to the condenser coil, which releases it. Fans move air over both coils. If either coil cannot breathe, the system runs longer, gets hotter and eventually stops.

Where the condenser sits matters in a small kitchen. Reach-ins, prep tables and many ice machines are self-contained and dump their heat into the room. Walk-ins usually have a remote condensing unit on top of the box, in the cellar or on the roof.

1 2 3 4 5 6

A walk-in cooler in section

  1. Evaporator coil and fans. Cold air leaves here and must be able to circulate.
  2. Condensing unit: compressor, condenser coil and fan.
  3. Door gasket and closer. The door should pull itself shut and seal all round.
  4. Strip curtain. Cuts the air exchanged each time the door opens.
  5. Evaporator drain line, trapped and run to a drain. In a freezer it is heated.
  6. Product on shelves, off the floor and clear of the evaporator's airflow.

Target temperatures

EquipmentTypical air temperatureWhy
Walk-in or reach-in cooler35 to 38°FKeeps food at or below the 41°F cold-holding limit in the FDA Food Code, with margin for door openings
Walk-in or reach-in freezer0°F or belowKeeps food frozen solid
Prep table railFood at 41°F or belowRails are open to kitchen air; keep lids down and pans not overfilled

Keep a thermometer inside every unit, away from the door, and log readings at opening and closing. A log shows a slow drift days before food is at risk, and health inspectors ask for it. Your local health code sets the limits that apply to you.

Clean the condenser coil

This is the single most useful task. Kitchen air carries grease, grease catches dust and flour, and the condenser's fins close up. The compressor then runs at higher pressure and temperature, uses more electricity and wears out early.

  1. Switch the unit off at its disconnect or unplug it.
  2. Find the coil: behind the lower or upper grille on a reach-in, on the condensing unit for a walk-in.
  3. Brush the fins in the direction they run with a soft coil brush, and vacuum the loosened dirt. Do not bend the fins.
  4. For grease, use a coil cleaner made for the purpose and follow its directions, or leave it to a technician.
  5. Clear boxes and bags from around the unit so air can reach it.

Monthly is a sensible interval in a working kitchen, and quarterly at the outside.

Door gaskets and closers

A torn or flattened gasket lets warm, humid air in every minute of the day. The signs are frost or water around the door frame, a compressor that rarely stops, and ice building on the evaporator. Close the door on a strip of paper; if it slides out with no drag, the seal is gone at that spot. Wipe gaskets weekly with mild soapy water, since grease and sugar make them brittle. Most gaskets on reach-ins press or slide into a channel and can be replaced without tools. Fix sagging hinges and weak closers at the same time, because a new gasket on a door that hangs crooked will not seal.

Defrost

Any coil below freezing collects frost. Coolers usually clear it by stopping the compressor and letting the fans blow box air across the coil. Freezers need heat: electric heaters or hot refrigerant gas, run a few times a day by a timer or controller, with the fans held off until the coil is cold again.

When defrost fails, ice bridges the fins, airflow stops and the box warms up even though the system runs constantly. Common causes are a failed heater or timer, a termination sensor out of place, a frozen drain line, or simply too much moisture getting in through a bad door seal. Do not chip ice off a coil with a tool; the tubes puncture easily. Melt it, then find out why it formed.

Signs of trouble

What you noticeOften meansFirst step
Box temperature creeping up over daysDirty condenser, failing gasket, blocked evaporatorClean the coil, check the door, clear the airflow
Compressor runs without stoppingHeat getting in or not getting out; possibly low refrigerantCheck coils and doors, then call for service
Short, frequent starts and stopsControl or pressure problem, overheating compressorCall for service
Ice on the evaporator or box ceilingDefrost fault or air leakCheck gaskets and the defrost schedule
Water on the floor inside or under the unitBlocked or frozen drain lineClear the drain; check the drain heater on a freezer
Oily residue on tubing or fittingsRefrigerant leakCall for service. Do not top up and carry on
New buzzing, clicking or grindingFan motor, relay or compressor on its way outCall before it stops completely

Loading and daily habits

  • Leave space between product and the walls, and never stack in front of the evaporator.
  • Cool hot food down by an approved method before it goes in the walk-in. A stockpot of hot soup warms everything around it.
  • Keep doors shut during deliveries, or stage the delivery so the door opens once.
  • Check that walk-in lights go off with the door. They add heat.
  • Know where each unit's disconnect and breaker are before something goes wrong.

Refrigerant and who can work on it

Only a technician with EPA Section 608 certification may open a refrigerant circuit, add refrigerant or recover it. Older commercial systems commonly run on R-404A, which is being phased down, and many newer self-contained reach-ins use small charges of R-290, which is propane and needs its own handling. A system that needs topping up has a leak, and the right repair is to find and fix it. When an old walk-in system needs a compressor, ask about the refrigerant's future supply before paying for a major repair.

The heat your refrigeration removes ends up in the kitchen or on the roof, and the air conditioner pays for the part that stays indoors. The commercial cost-saving tips cover that side, including rooftop units and kitchen exhaust.